|
中兴ZXDU58W121室外一体化机柜,ZXDU58W121直流电源中兴ZXDU58W121室外一体化机柜,ZXDU58W121直流电源中兴ZXDU58W121室外一体化机柜,中兴ZXDU58W121直流电源 一.1.1 ZXDU58 W121通信电源系统的技术指标 ZXDU58 W121通信电源系统的外形如下图所示,技术指标见下表。ZXDU58 W121系列电源系统是户外型电源系统,高度为1.7米,允许输入电压在80 V~300 V之间。整个系统由ZXD1500 30A(V4.0)模块构成,满配置120A。先进的监控模块具有简易的动力环境监控功能,实现对温度、湿度、红外、水烟、门禁等环境量的监控,主要适用于中等容量需求的中心局站和基站控制器站点。 输入:220v-50/60HZ 32A 输出:-48V
made in china ZTE全球客户支持
图1.211 ZXDU58 W121通信电源系统外形图 表1.212 ZXDU58 W121通信电源系统的技术指标
防雷,空开,监控.
尺寸:1700mm×600 mm×600 mm 空调:HTI 70 2 散热量 700wk 加热 850 w 环境温度:-40+55度 额定电源 220v 50/ 60HZ 48v
中兴ZXDU58 W121系统是30 A(-48 V)系列通信电源产品。ZXDU58 W121系统具有强大的野外环境适应能力,可在户外的恶劣环境中使用;具有集中监控、电池维护和管理的功能,满足户外型智能无人值守的要求。
中兴ZXDU58 W121系统采用了国际上先进的整流器变换技术,能充分满足接入网设备、远端交换局、移动通讯设备、传输设备、卫星地面站和微波通讯设备的供电需求。
中兴ZXDU58 W121使用环境:
工作温度 -40℃ ~ +55℃
存储温度 -40℃ ~ +70℃
相对湿度 10%~90%
大气压 70 kPa ~ 106 kPa
场地要求 没有导电尘埃和腐蚀性气体,没有爆炸危险,没有震动颠簸,地板倾角≤5°
防水、防尘 IP55
中兴ZXDU58 W121交流配电:
额定输入电压 单相220 VAC/三相380VAC
可波动电压范围 80 VAC ~ 300 VAC(相电压)
频率 45 Hz ~ 65 Hz
输入电流 100 A
输入功率因数 ≥0.99(满载)
C级防雷泄放电流 ≤40 kA
D级防雷泄放电流 ≤20 kA
交流备用输出 2路。其中1路为单相三孔16 A维修插座;另1路为单相32 A交流备用输出,给电池柜加热板供电
中兴ZXDU58 W121直流配电:
输出电压 -42 VDC ~-58 VDC可调
输出电流 120 A(满配置)
负载输出 ***多6路,各路容量可为6 A~63 A
电池输入 2路电池输入,100 A空开
衡重杂音电压 <2 mV
峰-峰值杂音电压 ≤150 mV(20 MHz带宽)
效率 ≥90%(额定输入满载情况下)
直流防雷泄放电流 ≤5 kA
保护功能 可根据用户需要灵活配置一、二下电负载的路数
安全规格 符合IEC950标准
中兴ZXDU58 W121机柜尺寸和重量:
外形尺寸
组合机柜 600 mm×1745 mm×600 mm(宽×高×深)
分体机柜
整流柜: 600 mm×945 mm×600 mm(宽×高×深)
电池柜: 600 mm×945 mm×600 mm(宽×高×深)
重量
组合机柜 满配置时200 kg(不包括主设备和电池组)
分体机柜 满配置时整流柜130 kg(不包括主设备),电池柜70 kg(不包括电池组)
中兴ZXDU58 W121整流模块型号: ZXD1500(V4.0) -48V30A,满配可以配4个
中兴ZXDU58 W121监控模块型号: ZXDU58 B121
这个就是中兴室外电源ZXDU58 W121产品简介。
电池仓中兴ZXDU58 W121室外一体化机柜,中兴-48V高频开关电源.
中兴ZXDU58 W121室外一体化机柜,中兴-48V高频开关电源.
【直流电源】ZXDU58 W121整流器不工作故障处理 故障现象 某站点ZXDU58 W121组合电源在雷击后,整流器不能正常工作,但测量交流输入电压是正常的230 V,更换监控单元不能正常工作,只能由蓄电池供电,面临断站隐患。 故障分析 站点配置情况:ZXDU58 W121组合电源配置电池200 AH、BTS(一体化用铁笼基站)、没有机房和B级防雷。 现场调查发现,电源柜的防雷器已经被雷击全部损坏,监控单元BACK板有明显的烧坏痕迹。测量交流电压为230 V,零地电压为0 V,但整流器不工作。 根据上面现场调查情况后进行分析导致整流器不工作有两个方面原因: - 整流器本身问题。 由于该基站经过雷击难免会出现整流器本身损坏问题。 - 电源柜内部交流供电接线或部件损坏问题。 电源柜内供电接线故障特别要注意防雷器,因为防雷器的损坏可能导致交流零线无法连接到整流器。ZXDU58 W121电源内部交流输入接线关系示意如下图所示。 从上图可以分析,从交流输入端到整流器之间的零线是通过防雷器之间连接的。如果防雷器底座模块连接片掉了或雷击损坏,就会导致整流器之间零线断开,从而导致整流器不能正常工作。 故障处理 1. 在现场更换了新的整流器,仍不能正常工作。 2. 在电源柜上的交流备用空开上取电单独接到整流器上,可以正常工作。从而可以排除整流器问题。 3. 检查电源柜内部接线,目测检查中没有发现问题。 4. 用万用表检测连接线,发现从交流主空开到整流器插头上的零线不通,闭合开关也是同样情况(主空开无故障)。从而说明电源柜内主空开到整流器插座之间的零线没有接通。 5. 进一步检查发现接到整流器插座的零线是连接在防雷器底座零线端子上,由于雷击原因导致防雷器损坏。用户自行把防雷器两个模块之间的连接铜片丢掉,从而导致输入零线与整流器插座零线不能连接。 6. 更换防雷器底座后故障消除,插上整流器后系统正常工作。 总结 在熟悉内部连接图的前提下,按照交流电的流向,一步一步检查线路导通状况,排除故障。 【直流电源】ZXDU58 W121整流器不工作故障处理
DC power supply ZXDU58 W121 rectifier not working fault handling Failure phenomenon After lightning strike, the rectifier of ZXDU58 W121 combined power supply at a certain station can not work properly, but the AC input voltage is normal 230V. The replacement monitoring unit can not work properly. It can only be powered by accumulator, facing the hidden danger of station interruption. fault analysis Site configuration: ZXDU58 W121 combined power configuration battery 200 AH, BTS (integrated cage base station), no computer room and B class lightning protection. Field investigation shows that the lightning protection of the power cabinet has been damaged by lightning strike, and the BACK board of the monitoring unit has obvious burning marks. The AC voltage is 230 V and the zero earth voltage is 0 V, but the rectifier is not working. There are two reasons why the rectifier does not work on the basis of the above investigation. - rectifier itself. The damage of the rectifier itself will inevitably occur after the base station is struck by lightning. - power supply cabinet internal AC wiring or parts damage. Special attention should be paid to lightning protectors when power supply connection fails in power cabinets, because the damage of lightning protectors may lead to AC zero line can not be connected to the rectifier. ZXDU58 W121 power supply internal AC input wiring relationship as shown below. As can be seen from the above diagram, the zero line from the AC input to the rectifier is connected by lightning arresters. If the connector of lightning arrester base module is dropped or damaged by lightning strike, the zero line between rectifiers will be disconnected, and the rectifier will not work properly. Troubleshooting 1. the replacement of the new rectifier at the scene is still not working properly. 2. on the power supply cabinet, the AC standby switch will be connected to the rectifier separately, and it will work normally. Thus the rectifier problem can be excluded. 3. check the internal wiring of the power cabinet. No problems were found in the visual inspection. 4. Using a multimeter to check the connection line, it is found that the zero line from the AC main air to the rectifier plug is impassable, and the closed switch is the same (the main air is open without fault). Thus, the zero line between the main air and the rectifier socket in the power cabinet is not connected. 5. Further inspection found that the zero line to the rectifier socket is connected to the zero line terminal of the lightning protector base, resulting in damage to the lightning protector due to lightning strike. The user discards the copper sheet of the connection between the two modules of the lightning arrester, which causes the input zero line to be unable to connect with the rectifier socket zero line. 6. after replacing the base of the lightning arrester, the fault will be eliminated, and the system will work normally after plugging in the rectifier. summary On the premise of familiar with the internal connection diagram, according to the AC flow direction, step by step check the line conduction status, troubleshooting |