华为高频开关电源厂家销售价格 TP48400B电源价格

 TP48400B Overview

1.1 Composition and Configurations

1.2 Working Principles

1.3 Component Description

1.3.1                          Rectifier R4850G2

1.3.2                          Rectifier R4850G1 and R4850N1

1.3.3                          SMU02B

1.3.4                          UIM02C

1.4 Monitoring Network

2 Engineering Design

2.1                                     Design Drawings

2.2                                     Cable Configuration Principles

2.3                                     Methods of Calculating the Number of Rectifiers

2.3.1                          Method of Calculating rectifiers for EconomicConfiguration

2.3.2                          Method of Calculating Rectifiers for StandardConfiguration

2.4                                     Method of Calculating Battery Capacity

2.5                                     Schematic Diagrams

3 Installation

3.1                                     Installation Preparations

3.2                                     Installation

3.2.1                          Mechanical installation

3.2.2                          Electrical Installation

3.3                                     Installation Verification

3.4                                     Powering On and Commissioning

3.5                                     Acceptance

3.5.1                          Installation Acceptance

3.5.2                          Electricity Acceptance

3.5.3                          PSU Acceptance

3.5.4                          SMU Acceptance

3.5.5                          Parameter Acceptance

3.5.6                          Performance Acceptance

Panel

The front panel provides a Power indicator, an Alarm indicator, and a Fault indicator. Figure 1-9 shows the rectifier front panel. Table 1-3 describes the indicators on the panel.

Figure1-9              R4850G2 Rectifier panel

(1) Power indicator

(2) Alarm indicator

(3) Fault indicator

(4) Latch

(5) Handle


 

Table 1-3 Indicator description

Indicator

Color

Status

Description

Power indicator

Green

Steady on

The rectifier has an AC input.

Off

The rectifier has no AC input.

The rectifier is faulty.

Blinking at 0.5 Hz

The rectifier is being queried.

Blinking at 4 Hz

The rectifier is loading an application program.

Alarm indicator

Yellow

Off

The rectifier generates no alarms.

Steady on

The rectifier generates an alarm for power limiting due to ambient overtemperature.

The rectifier generates an alarm for protection or shutdown due to ambient overtemperature or undertemperature.

The rectifier protects against AC input overvoltage or undervoltage.

The rectifier is hibernating.

Blinking at 0.5 Hz

The communication between the rectifier and the monitoring unit is interrupted.

Fault indicator

Red

Off

The rectifier is working properly.

Steady on

The rectifier shuts down due to output overvoltage.

The rectifier has no output due to an internal fault.

 

Technical Specifications

Table 1-4 describes the rectifier technical specifications.

Table 1-4 Rectifier technical specifications

Item

R4850G2

Efficiency

The peak point is˃96%;

≥95% (230 V AC, 30%–100% load)

Output power

3000 W (176-290 V AC);

1250 W (85-175 V AC decreased linearly)

Dimensions (H x W x D)

40.8 mm x 105 mm x 281 mm

(1.61 in. x 4.13 in. x 11.06 in.)

Weight

≤2 kg